The HST-150-5-5-A-1.5K speed probe is used for speed measurement, zero-speed monitoring and overspeed protection of large rotating machinery such as steam turbines, compressors, fans and water pumps. It is an active sensor that requires external power supply. It outputs well-shaped pulse signals and can be directly connected to TSI systems, ETS systems, DCS or PLC acquisition modules.
Main Technical Features of HST-150-5-5-A-1.5K Speed Probe
- Non-contact measurement There is no physical contact between the probe and rotating parts, resulting in zero wear and long service life.
- Zero-speed detectable Compared with magnetoelectric sensors, Hall sensors can detect speed starting from a static state, which is suitable for zero-speed monitoring.
- Standardized output signal Square wave / pulse output with stable amplitude independent of rotating speed and strong anti-interference capability.
- Excellent environmental adaptability The sealed structure resists oil contamination, dust and moisture, suitable for harsh working conditions in power plants, petrochemical industries and other sites.
- High response frequency Covers the range from extremely low speed to high speed, meeting the fast response requirements for steam turbine overspeed protection.
Installation and Maintenance Notes for HST-150-5-5-A-1.5K Speed Probe
- Air gap adjustment The gap between the probe end face and the gear tooth tip shall be kept within the range specified by the manufacturer (typically 1~3 mm). Lock the anti-loosening nut after installation to prevent gap variation caused by vibration.
- Aligned installation The axis of the probe shall be as perpendicular as possible to the gear end face. Excessive deviation will degrade signal quality.
- Wiring specifications Shielded cables shall be used for power and signal wires. The shield layer shall be single-point grounded, and cables shall be routed away from power cables.
- Gear requirements The trigger gear shall be made of magnetically permeable material with uniform tooth profile. The number of teeth shall match the setting value of the rear instrument.
- Routine maintenance Periodically check whether the probe fastening is loose and whether the cable is damaged. Clean the probe end face during unit overhaul to ensure no iron scraps or oil contamination adhere to it.